House Service Cut Outs
Devices accepting BS 1361 cylindrical cartridge fuses having separate Neutral and Earth blocks.
60/80A rated / 100A rated.
Features at a glance
- Separate Neutral and Earth blocks interconnectable with the link provided
- Two incoming and outgoing Phase and Neutral terminations which accept up to 35mm2 conductors in either copper or aluminium, stranded or solid
- Silver plated Phase terminal contact block
- Serrated bores on Phase/Neutral terminal contact blocks with two M8 hexagon drive pinching screws per conductor
- Two incoming and two outgoing terminals on Earth block each accepting up to 25mm2 conductors
- Safety interlocked mouldings. N/E cover moulding cannot be removed until fuse carrier has been withdrawn
- Sealing wire facility
- Blanking plugs for unused cable entries provided
- Additional accessories include cable cover, cable sealing chamber and busbar extensions
Construction
- Body, base and cover - Glass re-inforced polyester DMC in RAL 7035 colour
- Terminal blocks - Brass (silver plated on Phase)
- Fuse link contacts - Copper
Performance
- Rated voltage - 240/415V a.c.
- Max rated current - 100A
- Supply frequency - 50-60Hz
- Flammability rating - UL VO, self-extinguishing
30 seconds at 960 degrees C
- Recommended terminal torque - 2.25Nm
- Fuse short circuit rating - 33kA at 0.3pf
Conformity to Standards
- Conforms to BS 7657:1993
- Accepts fuse links in accordance with BS 1361:1991
Weights and Dimensions
- Height - 98mm
- Width - 106mm
- Depth - 96mm
- Weight (excluding fuse) - 0.82kgs
Links
Cable Services web link: House Service Cut Outs
Data Sheet PDF: House Service Cut Outs
Cable Services Catalogue PDF: House Service Cut Out Products
Service Connections Sales Enquiry
Cable Services are able to offer full technical support for the full product range of service connection products.
Please contact one of our sales offices for product information and technical specifications.